Output behaviour decides what the machine does when the operator takes a thumb off the button. A crane remote control can be built with momentary outputs, maintained outputs or toggle outputs, and the same transmitter body will carry any of the three. Momentary means the output is energised only while the button is held. Maintained means it latches on until it is deliberately switched off. Toggle means each press flips the state and the next press flips it back.
Almost every crane motion has to be momentary, and most enquiries that go wrong on this point go wrong because the buyer described a button instead of describing a behaviour. This guide explains what each behaviour does, where the non-momentary versions are genuinely correct, how the behaviour interacts with the receiver hardware, and how to write the requirement so the supplier builds what you meant.

What each output behaviour actually does
With a momentary output the answer is that the output drops immediately and the contactor opens. With a maintained output nothing changes — the output stays energised until a separate stop action, an emergency stop, or a dedicated off button interrupts it. With a toggle output the press that started the function has also armed the next press to stop it, so the function stays on until the same button is pressed again.
| Behaviour | On release | Correct use on a crane | What it looks like if misapplied |
|---|---|---|---|
| Momentary | Output drops at once | Travel, hoist up and down, trolley, all motion functions | None — this is the default and the safe choice |
| Maintained | Output stays on | Lighting, a hydraulic power pack, a pump, an exhaust fan | Motion that keeps running after the operator lets go |
| Toggle | State flips on the next press | Two-state ancillaries where a second button is inconvenient | A runaway function that reacts to the wrong press |
Terminology varies between suppliers and causes a surprising share of order errors. “Non-latching”, “spring-return” and “self-resetting” all mean momentary. “Latching” and “self-locking” mean maintained. “Alternate action” means toggle. When a datasheet uses one of these words without a timing statement, ask for the release behaviour in plain language rather than assuming the term means what you expect.
Why almost every crane motion must be momentary
A crane is not a machine that does a cycle on its own. The operator is steering a load through space while watching the load, not the button. Hands come off buttons constantly — to look, to signal a colleague, to change grip, to step sideways with a swinging load. Every one of those moments is a moment when the machine must stop.
The regulatory logic points the same way. Motion control is expected to follow a hold-to-run principle, and an emergency stop is only a backup to that principle, not a substitute for it. A maintained hoist output means the emergency stop becomes the only way to stop the load, which turns a routine action into a high-stakes one and puts the most-used control in the path of the least-practised action.
If a site has inherited a transmitter where one motion function is maintained, treat it as a defect rather than a preference. It is normally a configuration error from a unit that was ordered for a different duty, and it is fixed in the receiver configuration or by replacing the receiver board, not by changing how the operator works. A wired pedal obeys the same rule: the YDT1-16 dual foot switch gives two independent momentary pedals, which is exactly what a forward and reverse pair needs.
Where maintained and toggle outputs are correct
Maintained outputs earn their place on ancillaries. A work light on a gantry, a hydraulic power pack that needs to run ahead of any motion, a cooling fan, a warning beacon — these are functions where the operator wants a state rather than a movement, and where holding a button for an entire shift is neither sensible nor possible.
The important rule is that the maintained function must be structurally separate from motion. It should sit on its own button, ideally on a different key group, and it must be possible to leave it on without any motion output being enabled. Where the transmitter has a key-operated or slide-selected second level, ancillaries belong there rather than next to the hoist buttons.
Toggle outputs suit the same class of load where the function is genuinely two-state and the button count is tight. A grab that is either open or closed, a spreader that is either locked or unlocked — these read naturally as toggle. The caution is that toggle depends on the operator knowing the current state. On a grab, the state is visible. On a hydraulic clamp inside a machine guard it may not be, and there a maintained output with an indicator lamp, or a momentary output with a separate release, is easier to reason about.
For a system where the ancillary functions need this kind of separation, the ten-function industrial remote control is a common starting point because the extra buttons can be dedicated rather than shared. Machines that are not cranes follow the same rule, and a single pedal such as the YDT1-15 foot pedal switch is momentary for that reason.
How behaviour interacts with relay and solid-state outputs
Relay outputs are the default on crane receivers. They tolerate inrush, they fail open in the ordinary way, and they present a dry contact that any existing control circuit can accept. Solid-state outputs switch faster, have no contact to weld, and suit high-cycle duties — but they leak a small current when off, which matters on a circuit with a sensitive input, and they fail short more often than they fail open.
The pairing that causes trouble is a maintained command on a solid-state output that feeds a circuit expecting a relay. The leakage holds an input at a marginal level, the input reads it inconsistently, and the fault looks like an intermittent radio problem. The mechanism and the selection criteria are set out in relay versus solid-state receiver outputs.

What happens when you order the wrong behaviour
The failure is rarely dramatic and that is what makes it expensive. A maintained travel output produces a crane that keeps moving after the operator stops pressing, which is usually reported as “the remote sticks”. The operator compensates by stabbing at the stop button, the maintenance team replaces the transmitter, and the behaviour is unchanged because it was never in the transmitter.
The behaviour is also worth checking at the boundary between radio and the crane’s own control circuit. Where the receiver output feeds a control relay that is itself latching, a momentary radio command becomes a maintained machine command, and the radio is blamed for a logic error downstream. The cabinet side of that interface is covered in crane remote control wiring diagrams. Voltage matching across that interface is a separate trap, covered in control voltage selection. Vacuum retention is the clearest example of a function that must not be momentary, and the interlock logic behind vacuum lifters is what keeps a sheet on the beam when the link drops. The same momentary-or-maintained question applies upstream of the contactors, from foot pedals to cam changeover switches, which is how the control switch range is organised.
How to write the requirement into an enquiry
- List every function with the physical direction it commands, for example hoist up, hoist down, trolley left, trolley right, bridge forward, bridge reverse.
- Mark each function as momentary unless there is a specific reason otherwise, and state the reason for every exception.
- For each maintained or toggle function, state how it is turned off and whether an indicator on the transmitter is required.
- State whether the receiver output is a relay contact or a solid-state output for each group of functions.
- State how the outputs must behave when the radio link is lost, when the battery is removed, and when power is restored.
- Attach the existing control circuit diagram, or a description of any latching relay downstream of the receiver.
The two answers that most often change the build are the loss-of-signal behaviour and whether anything downstream latches. Both are properties of the crane, not of the remote, and both are answerable by the site electrician in a few minutes. If the crane is being retrofitted rather than newly equipped, the sequence in adding radio control to an existing crane covers where the behaviour check sits in the work.
If you are specifying a system and the function list is still being drafted, send the motion list and the ancillary functions and we will mark up the behaviour for each one before quoting. Start from the industrial crane remote control system range, or send the function list directly and we will return it annotated.
FAQ
Is momentary the same as a dead-man function?
No. A dead-man function is a supervisory condition that must be continuously satisfied for any motion to be possible, usually through a trigger, a lever or an enabling button. Momentary outputs are per-function. A crane normally has both: the dead-man condition enables the system, and each motion button is momentary within it.
Can a maintained output be changed to momentary later?
Usually yes, in the receiver configuration or by swapping the output board, and occasionally by changing the wiring at the terminal strip. It is not changed in the transmitter. Confirm the method with the supplier before ordering, because on sealed receivers the change may mean a factory reconfiguration.
Why do some suppliers quote a button count instead of a behaviour?
Because most catalogue units are momentary throughout and the behaviour never needs discussing. The question only appears when ancillaries, grabs or spreaders are involved, and at that point the supplier should ask rather than assume.
What should happen to a maintained output when the link is lost?
It should drop. A maintained function that survives a lost radio link is a function that cannot be stopped by the operator who is holding the transmitter, which defeats the purpose of the control. Specify drop-on-loss explicitly, because the default is not universal.